As the core means of transformer insulation status monitoring, oil dissolved gas chromatography analysis technology can achieve early warning of latent faults inside the equipment by accurately detecting the concentration changes of dissolved gas components in oil samples. This technology is based on the principle of gas chromatography separation. The implementation process includes: after extracting oil samples from the transformer body, degassing of dissolved gases is completed in a high vacuum environment, and quantitative analysis of each component is performed by the detector after separation by chromatographic column. According to GB/T 7252-2001 "Guidelines for Analysis and Judgment of Dissolved Gases in Transformer Oil", transformers with voltage levels of 220kV and below need to implement a periodic monitoring system, among which the key characteristic gas judgment thresholds are: hydrogen (H₂) reaches 150μL/L (may indicate low-energy discharge or electrolysis of water in oil), acetylene (C₂H₂) exceeds 5μL/L (a trace amount can represent high-temperature arc discharge of >800 Grad) und Gesamtkohlenwasserstoffe (Ch₄+c₂h₆+c₂h₄+c₂h₂) überschreiten 150 μl\/l (was auf mittlere und hochtemperaturüberhitzende Überhitzungsfehler hinweist).
Die Drei-Verhältnis-Methode (Rogers-Codierungsmethode) ist das zentrale Diagnosewerkzeug, das das Urteilsvermögen des Fehlertyps durch Berechnung der drei Gruppen von Verhältniscodierungskombinationen von Ch₄\/H₂, C₂h₂\/C₂h₄ und C₂h₄\/C₂h₆ realisiert. Die typischen Codierungskorrespondenzen umfassen: "0-3-2" Codepunkte auf schwere Überhitzungsfehler> 700 Grad, und "{1-0-2" Code zeigt eindeutig hohe Energie-Entladungsfehler an. Im Falle einer übermäßigen Gaskonzentration ist ein Schritt-für-Schritt-Behandlungsplan erforderlich: Verwenden Sie Vakuumölfiltrationsgeräte mit einer Verarbeitungskapazität von mehr als 5T\/h, kontrollieren<133Pa, and continue purification for ≥48 hours. Practice shows that after 48 hours of vacuum degassing treatment, the acetylene content of a 110kV transformer dropped from the excessive value to the qualified range. The supporting unidirectional circulation process (transformer → oil storage tank → oil filter → transformer) can construct a closed-loop purification path to achieve deep removal of dissolved gases. After the treatment is completed, it needs to be left to stand for 24 hours for retesting, and partial discharge test and insulation resistance test should be carried out simultaneously for double verification.
Die Ausrüstung, die zur Überholung in die Fabrik zurückgeführt wurde, muss eines der folgenden Kriterien erfüllen: Acetylenkonzentration> 10 μl\/l oder Gesamtkohlenwasserstoff> 300 μl\/l und die Drei-Rats-Methode-Diagnosen mit hoher Energienentladung (z. B. "1-0-2" Code); Bei der Inspektion der Demontage fanden interne Entladungsspuren (typischer Fall: Ein 220 -kV -Transformator wurde wegen einer Überholung in die Fabrik zurückgeführt, da die Wasserstoffkonzentration 800 μl\/l erreicht hat, und der Forschungs -Screen -Entladungsfehler des Buchse -Ends wurde schließlich bestätigt). Das vorbeugende Wartungssystem umfasst: Die erste chromatographische Analyse neu beauftragter Geräte muss nach 48 Stunden Ruhe durchgeführt werden. 220 KV-Transformatoren implementieren einen Halbjahresinspektionszyklus, und 110 kV-Geräte implementiert einen jährlichen Inspektionszyklus. Konzentration auf die Verstärkung der Aufrechterhaltung des Ölkissen -Dichtungssystems (der Fall der Wasserkraftstation Liyuan bestätigte, dass Dichtungsfehler die Hauptursache für den Standard war).
The partial discharge detection technology system covers two matrices: electrical measurement method and non-electrical measurement method: electrical measurement method includes pulse current method (IEC 60270 standard, 10pC-level sensitivity detection is achieved through Rogowski coil), ultra-high frequency detection method (UHF, deploying sensors in the flange gap of the box to capture 300 MHz -3 GHz Elektromagnetische Wellen), transiente Erdspannungsmethode (TEV, Erkennung von Nanosekundenspannungsimpulsen an der Außenwand der Box); Die nicht-elektrische Messmethode umfasst die Ultraschallpositionierungsmethode (40-200 kHz-Sensor-Array, um eine Zeitdifferenzpositionierung von ± 10 cm Ebene zu erreichen), optische Messmethode (eingebauter optischer Fasersensor zur Erfassung von Entladungslichtstrahlung), chemischer Nachweis (mit Ölchromatographie, IT-Abfall-Abfall-Abfall-Risiko) und TRACE-C ₂h ₂ H ₂-detailliert.
Die intelligente Diagnosetechnologie umfasst Multi-Source-Informationsfusion, Deep-Learning-Anwendung und digitales Twin-System: Eine Umstation von 75 0 KV identifizierte erfolgreich 0,5-mm-Micro-Gap-Entladung in der Buchse durch UHF+Ultrasound+Ölchromatographie-Gelenküberwachung; Das auf dem ResNet -Netzwerk basierende Deep -Lern -Modell erreichte eine Entladungsmustererkennungsgenauigkeit von 96%. Das digitale Twin-System konstruierte ein dreidimensionales elektromagnetisch-thermisch-mechanisches Kopplungsmodell, um die dynamische Vorhersage des Entladungsentwicklungsprozesses zu erreichen. In einem Anwendungsbeispiel einer Wandlerstation im südlichen Stromnetz im Jahr 2023 ergab die Überwachung der Ölchromatographie, dass die C₂H₂ -Konzentration 8,2 μl\/l erreichte und die synchrone UHF -Erkennung typische Entladungssignale erfasste. Die Ultraschallpositionierung sperrte den Fehlerpunkt der B-Phase-Buchse genau ab. Die Inspektion der Demontage bestätigte, dass die Lockerung des Bewertungsrings aufgehängte Entladung verursachte. Nach der Reparatur wurde die Entladung der Ausrüstung von 3500 PC auf 15 Prozent erheblich reduziert.
In der Forschungsergebnis wurde darauf hingewiesen, dass eine moderne Diagnose der Verwerfungsdiagnose eines dreidimensionalen Überwachungssystems der "Ölchromatographie initialen Screening-Multi-Technologie-Positionierungsbewertung" aufbauen sollte. Basierend auf der Ölchromatographieanalyse als grundlegende Überwachungsmethode in Kombination mit UHF\/Ultraschallpositionierungstechnologien kann eine genaue Diagnose von Entladungs- und Überhitzungsfehlern erreicht werden. Die zukünftige Entwicklung sollte sich auf die Konstruktion digitaler Twin -Systeme in Verbindung mit mehreren physischen Feldern konzentrieren und das intelligente Maß an Stromnetzgeräte und Wartung durch dynamische Isolationsstatusbewertung und Lebensdauer umfassend verbessern.